Emergency Patrolling

Patrol Tasks
Scheduled
48
42
Completed
43
▲ 13% MoM
Overdue
5
▲ 25% MoM
Defects
Found
29
▲ 12% MoM
Critical
14
▲ 17% MoM
Completed
20
▲ 18% MoM

Monthly Patrols

Defects Found vs Critical

29
Critical:14
Non-Critical:15
Completed:20

Most Common Defects — Circuit-1

Nature of Defect
Snapping of Conductor3
Snapping of Earthwire2
Burnt Trees3
Trees Likely to Cause Tripping2
Dead Bird Found2
Flashover on Insulator / Fittings3
De-capping of Insulators2
Burnt Jumpers2
Any Foreign Material on / Below Line2
Any Other Defect / Abnormality Observed1

Most Common Defects — Circuit-2

Nature of Defect
Snapping of Conductor2
Snapping of Earthwire2
Burnt Trees2
Trees Likely to Cause Tripping3
Dead Bird Found1
Flashover on Insulator / Fittings2
De-capping of Insulators2
Burnt Jumpers2
Any Foreign Material on / Below Line2
Any Other Defect / Abnormality Observed

Patrol Records

Work OrderTowerTower TypeLineTripping Date / TimePersonDefects FoundRemarks
WO-2025-901T-089DD+09 LTJaigad–KaradMar 14, 2025 02:18Rajesh K.1Conductor snapping on Circuit-1, middle phaseView
WO-2025-902T-134DA+03 RTJaigad–New KoynaMar 12, 2025 19:42Anil P.1Flashover on insulator string, top phaseView
WO-2025-903T-220DB+05 LTJaigad–KaradMar 11, 2025 06:05Suresh M.2Burnt trees below line, ROW encroachmentView
WO-2025-904T-034DC+02 RTJaigad–New KoynaMar 09, 2025 23:11Deepak N.1Dead bird found, no permanent damageView
WO-2025-905T-145DD+09 LTJaigad–KaradMar 07, 2025 14:33Vikram R.1Earthwire snapping near top hamperView
WO-2025-906T-256DA+01 RTJaigad–New KoynaMar 05, 2025 09:27Rajesh K.1Burnt jumper on Circuit-2, no tripping cause confirmedView
WO-2025-907T-067DB+08 LTJaigad–KaradMar 03, 2025 21:50Anil P.2Foreign material (kite string) on lineView
WO-2025-908T-178DC+06 RTJaigad–New KoynaMar 01, 2025 03:14Suresh M.2De-capping of insulators observed, top phaseView